Fan static pressure, total pressure and system resistance

Static pressure and total pressure are not interchangeable. Total pressure includes static pressure and velocity pressure at the same reference point. System resistance is the pressure lost through ducts, fittings and equipment.

4-72 centrifugal fan for a duct system pressure example

Static pressure and total pressure are not interchangeable. Total pressure includes static pressure and velocity pressure at the same reference point. System resistance is the pressure lost through ducts, fittings and equipment.

An RFQ should state which pressure is required, where it applies and at what airflow. Without that context, two identical numbers may describe different duties.

Static pressure

Static pressure describes the pressure potential acting on the duct walls. Designers often use it when calculating the pressure needed to overcome duct and equipment resistance. Terms such as external static pressure and fan static pressure may use different boundaries, so the definition needs to be stated.

Velocity pressure

Velocity pressure depends on air speed. The same airflow through a smaller area produces higher velocity and higher velocity pressure. Connection size therefore matters when pressure values are compared.

Total pressure

At one reference point, total pressure is the sum of static and velocity pressure. Fan total pressure describes the total mechanical energy added to the airstream. Selecting from a total-pressure curve when the schedule specifies static pressure, or the reverse, can shift the actual duty point.

System resistance

Straight duct, elbows, branches, transitions, dampers, louvres, filters, coils, silencers and treatment equipment all add pressure loss. Dirty filters or changed damper positions alter the system curve during operation.

The most useful RFQ includes an itemised resistance schedule. If only one pressure value is available, state whether it includes final filter resistance, silencers, outlet velocity pressure and design margin.

Pressure data checklist

  • Static or total pressure
  • Units and reference points
  • Design airflow and air density
  • Duct and fitting losses
  • Clean and dirty filter resistance
  • Equipment and silencer losses
  • Included design margin